PC 113
Certificate Details
- Certificate Number: PC 113
- Document ID: UNIM150222
- Expiration: Thursday, 14 February 2030
Main Certification Holder Details
- Company Name: Unimix Block Industry LLC
- Company Address: P.O. Box 54131, Dubai, United Arab Emirates
- Participating Site(s): UNIMIX BLOCK INDUSTRY LLC
P.O. Box 54131, Road No. 60, Plot No. 599-641, Jebel Ali Industrial Area 2, Dubai, United Arab Emirates - Nominated Agent(s): NONE
Certification Details
- Scheme: Q-Plus Product Conformity Scheme for Fire Building Enclosure
- Certificate Status: Active
- Certification Type: Multisite Certification
- Certificate maintenance: Validity of the Certificate is subject to Yearly / 6 month Surveillance Audit
- Surveillance Audit Status: No Pending
Scope of Certification
| Test Report Ref. | Product Description | Tested Results/ Properties | Test Standard | |
| Integrity | Insulation | |||
| ML_520606 SN 1/1 (161123384) | UNIMIX_4" Solid Concrete Blocks – Non-Loadbearing Wall | 240 minutes | 89 minutes | BS 476: Part 22:1987 Amd. 2014 |
| ML_CR-1803/4644 SN 1/1 (180321587) | UNIMIX_4" Hollow Concrete Blocks – Non-Loadbearing Wall | 240 minutes | 240 minutes | BS 476: Part 22:1987 Amd. 2014 |
| ML_523427 SN 1/1 (161214397) | UNIMIX_6" Solid Concrete Blocks – Non-Loadbearing Wall | 240 minutes | 190 minutes | BS 476: Part 22:1987 Amd. 2014 |
| TBWIC_MA44-02, Rev.01 | UNIMIX_6" Hollow Concrete Blocks - Non-Loadbearing Wall | 240 minutes | 112 minutes | BS 476: Part 22: 1987 |
| TBWIC_NL 74-1, Rev.01 | UNIMIX_8" Solid Concrete Blocks – Non-Loadbearing Wall | 240 minutes | 240 minutes | BS 476: Part 22: 1987 |
| TBWIC_MA44-01, Rev.01 | UNIMIX_8" Hollow Concrete Blocks – Non-Loadbearing Wall | 240 minutes | 169 minutes | BS 476: Part 22: 1987 |
| ML_FRQ-1812/1566 SN 1/1 (181206593) | UNIMIX_8” Thermal Concrete Hollow Blocks – Non-Loadbearing Wall | 240 minutes | 240 minutes | BS 476: Part 22:1987 Amd. 2014 |
| TBWIC_NL 74-2, Rev.01 | UNIMIX_10" Thermal Concrete Hollow Blocks - Non-Loadbearing Wall | 240 minutes | 240 minutes | BS 476: Part 22: 1987 |
approval from CCS. Any violation of this requirement will invalidate existing test reports and certification approvals.
· Test reports shall not be combined with primary FoA reports. It is crucial to follow the test reports precisely to ensure accurate results and reliable product performance.