PC 313 - Certification, Testing, Fire Test, Inspection, Training and Technical Services | CCS Conformity Certification Services

PC 313

  • Certificate Details

  • Certificate Number: PC 313
  • Document ID: PORT230224-FD
  • Expiration: Thursday, 22 February 2029
  • Main Certification Holder Details

  • Company Name: PORTA CORE EXPERTS FIRE RESISTANT DOORS MANUFACTURING LLC
  • Company Address: P.O. Box 111156, Dubai Investment Park 2, Dubai, United Arab Emirates
  • Certification Details

  • Scheme: Q-Plus Product Conformity Scheme for Fire Door
  • Certificate Status: Active
  • Certification Type: Single Site Certification
  • Certificate maintenance: Validity of the Certificate is subject to Yearly / 6 month Surveillance Audit
  • Surveillance Audit Status: No Pending

Scope of Certification

Test Report Ref. Product Description Tested Results/Properties Test Standard
Integrity Insulation Other
TBWIC_XF091-1A (Rev. 02) Porta Core_Latched, Single-Acting Single Leaf Wooden Doorset with Steel Frame_52mm thick Fireblock Dura-L40/SR70 Door Blank_Non-Loadbearing Assembly 20 / 45 / 60 minutes - Hose Stream = No Failure UL 10C:2016
TBWIC_WI045-1B (INTERTEK_01279082SHJ-002) Porta Core_Latched, Single-Acting Double Leaf Wooden Doorset with Wooden Frame with or without Vision Panel _52mm thick Fireblock Dura L40 Core_Non-Loadbearing Assembly 20 / 45 / 60 / 90 minutes (without vision panel) 20 / 45 minutes (with vision panel) - Hose Stream = No Failure UL 10C:2016
ML_FRR-2303/6331 C2-2 (2303221059) Porta Core_Latched, Single-Acting Single Leaf Wooden Doorset with or without Vision Panel_ 54mm thick ALTUS FD-60 Core_Non-Loadbearing Assembly_SP1 60 minutes 30 minutes (Up to 44 minutes) - BS 476 Part 22: 1987 Amd. 2014
TBWIC_XF091-3A Porta Core_Latched, Single-Acting Single Leaf Wooden Doorset with Steel Frame_52mm thick Fireblock Dura-L40/SR70 Door Blank_Non-Loadbearing Assembly 60 minutes 60 minutes - BS 476 Part 22: 1987 Amd. 2014
TBWIC_XF091-4A Porta Core_Latched, Single-Acting Single Leaf Wooden Doorset with Wooden Frame _ 52mm thick Fireblock DURA-F40 Frame & 52mm thick Fireblock DURA L40-FMB Door Blank_Non-Loadbearing Assembly 60 minutes 60 minutes - BS 476 Part 22: 1987 Amd. 2014
ML_FRR- 2403/481 C1-2 (2401151128) Porta_Latched, Single-Acting Double Leaf Wooden Doorset with or without Vision Panel_52mm thick Fireblock ALTUS -FMB Door Blank Non-Loadbearing Assembly 90 minutes (Up to 92 minutes) 90 minutes (Up to 92 minutes) - BS 476 Part 22: 1987 Amd. 2014
ML_FRR- 2403/480 C1-2 (2401241131) Porta_Latched, Single-Acting Double Leaf Wooden Doorset with or without Vision Panel_54mm thick ALTUS FD-60 Core_Non-Loadbearing Assembly 60 minutes (Up to 62 minutes) 60 minutes (Up to 62 minutes) - BS EN 1634-1: 2014 + A1: 2018
ML_FRR-2306/1427 (2401201130) Porta Core_Latched, Single-Acting Double Leaf Wooden Doorset with or without Vision Panel_ 64mm thick Fireblock Altus FD-90 Core_Non-Loadbearing Assembly 90 minutes (Up to 95 minutes) 90 minutes (Up to 95 minutes) Radiation = 90 minutes (Up to 95 minutes) BS EN 1634-1: 2014 + A1: 2018
ESL_0321-25-TR-01/A Porta Core_Latched, Single-Acting, Single Leaf Wooden Doorset with Wooden Frame with or without Vision Panel_54mm thick Altus FD-60 Core_Non-Loadbearing Assembly 90 minutes - Radiation = 90 minutes EN 1634-1: 2014+A1 2018
ESL_0321-25-TR-01/A Porta Core_Latched, Single-Acting, Single Leaf Wooden Doorset with Wooden Frame with or without Vision Panel_54mm thick Altus FD-60 Core_Non-Loadbearing Assembly 60 minutes - Radiation = 60 minutes EN 1634-1: 2014+A1 2018
ML_FRR-2405/8540 (2503221189) Porta Core_Latched, Single-Acting, Single Leaf Wooden Doorset without Vision Panel_46mm thick Fireblock Dura L40/SR60-N_Non-Loadbearing Assembly_SP01 60 minutes - Hose Stream = No Failure UL 10C:2016 (R2021)
ML_FRR-2405/8540 (2503221189) Porta Core_Latched, Single-Acting, Single Leaf Wooden Doorset without Vision Panel_54mm thick Fireblock Dura L40/SR60_Non-Loadbearing Assembly_SP02 60 minutes - Hose Stream = No Failure UL 10C:2016 (R2021)
·          No alterations shall be made to any product specifications or parameters mentioned in the test report such as design, components, performance criteria without prior approval from CCS. Any violation of this requirement will invalidate existing test reports and certification approvals.
·          Test reports shall not be combined with primary FoA reports. It is crucial to follow the test reports precisely to ensure accurate results and reliable product performance.
back to top