PC 190 - Certification, Testing, Fire Test, Inspection, Training and Technical Services | CCS Conformity Certification Services

PC 190

  • Certificate Details

  • Certificate Number: PC 190
  • Document ID: INTE071018
  • Expiration: Saturday, 06 October 2029
  • Main Certification Holder Details

  • Company Name: INTERMETAL LLC
  • Company Address: P.O Box 474039, Dubai Investment Park 1, Dubai, United Arab Emirates
  • Certification Details

  • Scheme: Q-Plus Product Conformity Scheme for Fire Door
  • Certificate Status: Terminated
  • Certification Type: Single Site Certification
  • Certificate maintenance: Validity of the Certificate is subject to Yearly / 6 month Surveillance Audit
  • Surveillance Audit Status: Overdue Audit

Scope of Certification


Test Report Ref.
Product Description Tested Results/ Properties Test Standard
Integrity Insulation
ML_TPWR-1808/713 C1-2 SN 1/1 (180702504) Intermetal_Latched, Single Acting, Solid Hardwood Frame and Single Leaf Doorset without Vision Panel_54mm thick FireBan 60 Core_Non-Loadbearing Assembly_SP1 60 minutes (up to 81 minutes) 60 minutes (up to 81 minutes) BS 476 Part 22:1987 (Amd. 2014)
ML_TPWR-1808/713 C1-2 SN 1/1 (180702504) Intermetal_Latched, Single Acting, Single Leaf Wooden Doorset with MDF Frame and without Vision Panel_54mm Thick FireBan 60 Core_Non-Loadbearing Assembly_SP2 60 minutes (up to 80 minutes) 60 minutes (up to 80 minutes) BS 476 Part 22:1987 (Amd. 2014)
ML_FRR-1901/4114A C1-2 SN 1/1 (190110608) Intermetal_Latched, Single Acting, Single Leaf Wooden Doorset with or without Vision Panel_64mm thick FireBan 90 Core_Non-Loadbearing Assembly_SP1 90 minutes (up to 98 minutes) 90 minutes (up to 98 minutes) BS 476 Part 22:1987 (Amd. 2014)
ML_FRR-1901/4114A C1-2 SN 1/1 (190110608) Intermetal_Latched, Single Acting, Single Leaf Wooden Doorset with MDF Frame without Vision Panel_64mm thick Fire Ban 90 Core_Non-Loadbearing Assembly_SP2 90 minutes (up to 97 minutes) 90 minutes (up to 97 minutes) BS 476 Part 22:1987 (Amd. 2014)

·         No alterations shall be made to any product specifications or parameters mentioned in the test report such as design, components, performance criteria without prior approval from CCS. Any violation of this requirement will invalidate existing test reports and certification approvals.
·         Test reports shall not be combined with primary FoA reports. It is crucial to follow the test reports precisely to ensure accurate results and reliable product performance.

 

Note: Q-Plus labels were issued. To verify, kindly send us directly an email from This email address is being protected from spambots. You need JavaScript enabled to view it. for the genuinity of Q-Plus Labels. 