Print this page

PC 269

  • Certificate Details

  • Certificate Number: PC 269
  • Document ID: NIAG09032022
  • Expiration: Friday, 08 March 2030
  • Main Certification Holder Details

  • Company Name: NIAGRA INTL WOOD IND. LLC
  • Company Address: P.O. Box 33131 Sharjah, United Arab Emirates
  • Participating Site(s): NONE
  • Nominated Agent(s): NONE
  • Certification Details

  • Scheme: Q-Plus Product Conformity Scheme for Fire Door
  • Certificate Status: Active
  • Certification Type: Single Site Certification
  • Certificate maintenance: Validity of the Certificate is subject to Yearly / 6 month Surveillance Audit
  • Surveillance Audit Status: No Pending

Scope of Certification


Test Report Ref.
Product Description Tested Results/ Properties Test Standard
Integrity Insulation
ML_FRR 2201/3569 (220110965) Niagra_Latched, Single Acting, Single Leaf Wooden Doorset without Vision Panel_54mm Thick Fire Ban Core FD60_Non-Load Bearing Assembly_SP1 60 minutes (up to 70 minutes) 60 minutes (up to 70 minutes) BS EN 1634-1:2014 + A1:2018
ML_FRR 2201/3569 (220110965) Niagra_Latched, Single Acting, Single Leaf Wooden Doorset with or without Vision Panel_54mm Thick Fire Ban Core FD60_Non-Load Bearing Assembly_SP2 60 minutes (up to 70 minutes) 60 minutes (up to 70 minutes) BS EN 1634-1:2014 + A1:2018
ML_FRR 2201/3570 (220112967) Niagra_Latched, Single Acting, Single Leaf Wooden Doorset with or without Vision Panel_64mm Thick Fire Ban Core FD90_Non-Load Bearing Assembly_SP1 90 minutes (up to 100 minutes) 90 minutes (up to 100 minutes) BS EN 1634-1:2014 + A1:2018
ML_FRR 2201/3570 (220112967) Niagra_Latched, Single Acting, Single Leaf Wooden Doorset with or without Vision Panel_64mm Thick FireBan Composite Core FD120_Non-Load Bearing Assembly_SP2 120 minutes (up to 132 minutes) 120 minutes (up to 132 minutes) BS EN 1634-1:2014 + A1:2018
ML_FRR 2201/3571 (220110966) Niagra_Latched, Single Acting, Double Leaf Wooden Doorset with or without Vision Panel_54mm Thick FireBan Core FD60_Non-Load Bearing Assembly 60 minutes (up to 70 minutes) 60 minutes (up to 70 minutes) BS EN 1634-1:2014 + A1:2018
ML_FRR 2201/3572 (220110968) Niagra_Latched, Single Acting, Double Leaf Wooden Doorset with or without Vision Panel_64mm Thick FireBan Core FD90_Non-Load Bearing Assembly 90 minutes (up to 92 minutes) 90 minutes (up to 92 minutes) BS EN 1634-1:2014 + A1:2018
ML_FRR-2403/7830 (2405031145) Niagra_Latched, Single Acting, Single Leaf Wooden Doorset with or without Vision Panel_50mm Thick Niagra Mineral Composite Door Blank 01 FD60_Non-Load Bearing Assembly_SP1 60 minutes (up to 68 minutes) 60 minutes (up to 68 minutes) BS EN 1634-1:2014 + A1:2018
ML_FRR-2403/7830 (2405031145) Niagra_Latched, Single Acting, Single Leaf Wooden Doorset without Vision Panel_50mm Thick Niagra Mineral Composite Door Blank 02 FD60_Non-Load Bearing Assembly_SP2 60 minutes (up to 69 minutes) 60 minutes (up to 69 minutes) BS EN 1634-1:2014 + A1:2018
ML_FRR-2403/7831 (2405031146) Niagra_Latched, Single Acting, Single Leaf Wooden Doorset with or without Vision Panel_54mm Thick Niagra Mineral Composite Door Blank 03 FD90_Non-Load Bearing Assembly_SP1 90 minutes (up to 100 minutes) 90 minutes (up to 100 minutes) BS EN 1634-1:2014 + A1:2018
ML_FRR-2403/7831 (2405031146) Niagra_Latched, Single Acting, Single Leaf Wooden Doorset with or without Vision Panel_60mm Thick Niagra Mineral Composite Door Blank 04 FD120_Non-Load Bearing Assembly_SP2 120 minutes (up to 121 minutes) 120 minutes (up to 121 minutes) BS EN 1634-1:2014 + A1:2018
ML_FRR-2403/7832 (2405041147) Niagra_Latched, Single Acting, Double Leaf Wooden Doorset with or without Vision Panel_60mm Thick Niagra Mineral Composite Door Blank 05 FD120_Non-Load Bearing Assembly 120 minutes (up to 124 minutes) 120 minutes (up to 124 minutes) BS EN 1634-1:2014 + A1:2018
·          No alterations shall be made to any product specifications or parameters mentioned in the test report such as design, components, performance criteria without prior approval from CCS. Any violation of this requirement will invalidate existing test reports and certification approvals.
·          Test reports shall not be combined with primary FoA reports. It is crucial to follow the test reports precisely to ensure accurate results and reliable product performance.